XX |
The AquaMatic 962 Stager
Controls combine an AquaMatic stager with an Autotrol 962 series electronic
control, mounted and prewired in a NEMA-rated enclosure. The
AquaMatic stager is a rotary pilot valve with multiple ports
for directing fluid flows to operate various diaphragm valves
installed in a water treatment system. AquaMatic stager internal
parts are constructed of durable, non-corroding, self-lubricating
materials for long, maintenance-free life.
Series 962 electronic controls provide sophisticated, demand-based water
treatment by combining a microprocessor with a flow meter to electronically
monitor the amount of water used. Time-based and/or external signal initiation
is also available as a standard feature.
This fully programmable series of controls provide the ability to fine-tune the
operation to meet the application requirements. |
Standard
Features
-
Accepts an input from a variety of flow sensors
to electronically monitor the amount of water used
-
Homing operation — The
control and stager automatically synchronize to the service
position
-
NEMA 4XFG fiberglass enclosure
-
115VAC 50/60Hz and 230VAC 50/60Hz available
-
Up to 15 programmable timed regeneration cycles
are available, programmable from 0 to 255 minutes
|
|
Single
Unit Controls |
Model
Number |
Description |
| Typical Softeners and Filters |
E948* |
962 Control with Model 48, 6-Port Stager |
| More Complex Softeners and Filters |
E951* |
962 Control with Model 51, 8-Port Stager |
|
Multiple
Unit Controls |
Model
Number |
Description |
| Twin Alternating Softeners and Filters |
E958-TA |
962 Control with Model 58-TA, 16-Port Stager |
| Sequential Filters (Backwash Only) |
E948 |
962 Control with Model 48, 6-Port Stager |
| 2 Unit Sequential Filters (Backwash & Rinse) |
E951 |
962 Control with Model 51, 8-Port Stager |
| 3 or 4 Unit Sequential Filters |
E958 |
962 Control with Model 58, 16-Port Stager |
Special
Features
-
Memory
Retention — During
a power outage, critical operating information is stored
in memory with no reprogramming required.
-
Capacity
Setting Lockout — The
control can be programmed to lock the capacity value so it
cannot be altered after installation.
-
Operating
Histories — Important
operating data is stored in memory and is retrievable upon
demand. The historical data includes peak flow data as well
as average daily usage for each day of the week.
-
US or Metric Units
of Measure
-
Multiple Initiation
Options
- Manual regeneration — A
separate REGEN button is provided for manual regenerations.
- Remote regeneration — A
set of terminals (with programmable delay) is provided
to allow for regeneration to be initiated from
a remote location.
- Calendar override — If
the volume of water has not caused a regeneration,
the 962 can be set to regenerate every one to thirty
days.
- Day of the week — Regeneration
on a specific day or days of the week with regeneration
occurring at a specific time of day (programmable).
- Volume of water used — With
regeneration occurring either immediately or delayed
to a specific time of day (programmable).
-
Selectable Reserve
Options
- Fixed reserve — The reserve
is fixed at a programmable percentage (30% factory
preset) of the total capacity.
- Variable reserve — The
controller monitors the daily water usage and at
the programmed time of regeneration, calculates the
average water used for each day of the week. The
reserve capacity is set to 120% of the average water
usage for the next day.
|
|