Industrial Valve Controls
swtwater.com A100 Series Stager Controls
Time initiated Controls for Filters and Softeners
NOTE: THIS PRODUCT LINE HAS BEEN DISCONTINUED.
REPLACEMENT PARTS MAY BE AVAILABLE. CONTACT YOUR SWT REPRESENTATIVE FOR MORE INFORMATION.
 
A100 Series Stager Control
DOWNLOAD OPERATION MANUAL
DOWNLOAD MATRIX & PROGRAM GUIDE
A100 Series Stager Controls combine an AquaMatic stager with an Autotrol timer, mounted and prewired in a NEMA enclosure.
The AquaMatic stager is a rotary pilot valve with multiple ports for directing fluid flows to operate various diaphragm valves installed in a process system. AquaMatic stager internal parts are constructed of durable, noncorroding, self-lubricating material for long, maintenance-free life. A100 controls have an integral time clock which is programmed to begin the regeneration process. Cycle times are programmable to accommodate a wide range of filter and softener applications.
Specifications  
Control Pressure 125 psi (8.6 bar)
Control Temperature 140°F (60°C)
 
 

Standard Features

  • Homing operation — The stager returns to service whenever the timer is in the service position.
  • NEMA 1 enclosure — NEMA 4 and NEMA 4XFG are also available.
  • 115VAC 60Hz, 230VAC 50/60Hz, and 24VAC 50Hz available.
  • Choice of 6-day or 7-day timer.
  • Maximum of 10 cycles programmable in 3 minute increments.
  • 102 minutes available.
 

Optional Features

  • Status lights
  • A dry or powdered contact closure can be provided during a cycle or cycles of operation on all models.
 
Applications
A100 Series Single Unit Controls
Model Number Description Applications
A148 A100 Control with Model 48, 6-Port Stager Typical Softeners and Filters
A151 A100 Control with Model 51, 8-Port Stager More Complex Softeners and Filters
 
A100 Series Multiple Unit Controls
Model Number Description Applications
A158-TA A100 Control with Model 58-TA, 16-Port Stager Twin Alternating Softeners
A148 A100 Control with Model 48, 6-Port Stager Sequential Filters (Backwash Only)
A151 A100 Control with Model 51, 8-Port Stager 2 Unit Sequential Filters (Backwash & Rinse)
A158 A100 Control with Model 58, 16-Port Stager 3 or 4 Unit Sequential Filters (Backwash & Rinse)
 
 
 
Safe Water Technologies, Inc.
996 Bluff City Boulevard
Elgin, IL 60120 USA
 
 
Telephone: +1.847.888.6900
Facsimile: +1.847.888.6924
E-mail: info@swtwater.com